Relay Settings in Real Power System: Requirements And Consideration

AllumiaX Engineering
9 min readNov 7, 2022

--

This blog consists of a discussion on the parameters and rules in the relay setting and how they are implemented.

The power system consists of generators, transformers, transmission lines, and other equipment whose costs is in millions of dollars. Power system equipment can severely be affected by faults, reducing their lifespan, or even getting burst or damaged which also reduces reliability and increases utility costs.

Power protection devices can be used to protect power systems equipment from getting damaged due to heavy faults and surges. Protective devices ensure the reliable operation of the system by sensing faults, surges, or any abnormal condition and according to the severity takes the right decision at the right time.

To configure protective devices such as making a relay setting, having all the consideration of the fault severity and decision-making time, it is important to know parameters, rules, and protection zone so that the reliability of the power system having continuous supply, is not compromised. Without prior knowledge of relay settings, reliability is affected badly and it can cause a penalty to the distributor.

Stay Sharp & Join our Mailing List!

Our surveys show that 90% of the people who join our blog have found the content valuable! Join today

Signup Now

Types of Relay

Based on Operating Mechanism:

  • Electromagnetic (mechanical type)
  • Static (electronics type)/ Solid State Relay
  • Microprocessor-based (programmable and communicating type)

We’ve also written a blog on Electromechanical Relays and Numerical Relays. If this grabs your interest, check it out and let us know your feedback.

Based on Actuating Parameter:

  • Overcurrent
  • Under/over voltage
  • Impedance
  • Under/over frequency

Based on Application:

  • Primary
  • Backup

Based on Protection Scheme:

  • Differential protection (difference in current)
  • Distance protection (V/I and time + distance)
  • Directional protection (time + direction of current)
  • Reverse power relay (negative sequence component)

Read this blog to learn more about Protection Schemes for Electrical Power Systems.

Overcurrent Relay

Overcurrent is the most used relay protective scheme as compared to others.

Definition:

An overcurrent relay works on sensing current. It operates whenever the current exceeds a permissible value or pickup value.

Layout:

An overcurrent relay works such that the system current is sensed by a current transformer (C.T). The primary side of C.T is connected to the system and the secondary side with a relay. In case of:

  • Fault/overload/ overcurrent: the relay operates and gives a trip signal to the breaker with respect to time.
  • No fault: the relay performs no operation

Types:

Be cleared to avoid damage to the apparatus. Following inverse time characteristics have been standarized.

  1. Inverse definite minimum time (IDMT) OC relay.
  2. Very Inverse time OC relay.
  3. Extremely inverse time OC relay

Characteristics of various over-current relays: (a) definite time, (b) IDMT, © very inverse, and (d) extremely inverse.

Common Terms:

1. Pickup Current (Ipu):

Definition:

Minimum amount of current required for the operation of the relay.

Objective:

Power system components work properly at a certain allowed current and when the magnitude of current exceeds a certain value (as in case of a fault), it can cause damage to the component and the entire system reliability is compromised. The relays are designed to operate above these rated currents. The pickup current is thus set at the maximum allowed current.

Formula:

Ipu = Rated CT output * %current setting

where,

Rated CT output is the rated current at the secondary side of the current transformer, typically 1A or 5A.

2. Current Setting:

Definition:

To adjust the pickup current (Ipu) to the desired value.

Objective:

C.T output comes in standard for example: 5A according to IEC and 1A according to IEEE.

The current setting sets the pickup value according to it so that the relay can operate at pickup current instead of working at rated C.T output

3. Plug Setting Multiplier (PSM):

4. Time Setting Multiplier (TSM):

5. Time/PSM Curve:

Click here to read detailed explanation of each Common Terms.

Calculation of Relay Operation Time

Procedure:

  • Step1: Calculating pickup-current.
  • Step2: Converting fault current into relay coil current by dividing fault current with C.T ratio.
  • Step3: Calculating PSM
  • Step4: From the time/PSM curve of a provided relay, determine the value of time of operation (at TSM=1) from the calculated PSM.
  • Step5: Multiplying the time from time/PSM curve with the required TSM to get the time of operation.

Solved Example:

Considering the following data:

C.T = 100 / 1

Breaker continuous current = 80 A

TSM = 50%

Fault current = 800 A

Time = 2s (at PSM=10 for time / PSM curve)

Solution:

Current setting = 80 / 100 (from eq2)

Current setting = 0.8 or 80%

Ipu = 1*0.8 (from eq 1)

Ipu = 0.8 A

Relay coil current = 800 / (100 / 1) (from eq 4)

Relay coil current = 8

PSM = 8 / 0.8 (from eq 3)

PSM = 10

top = 2 * 50 / 100 (from eq 5)

top = 1s

Principle of Time/Current Grading

A time/PSM curve for relays can be set in any of the three ways, which are described as:

Discrimination by Time:

A constant time setting is given to each relay irrespective of the magnitude of the current.

The issue with this method is that the relay closest to the source has the largest delay while it has the maximum fault current that could flow within the system, which can damage the system due to a large time delay.

Discrimination by Current:

This method is based on the phenomenon that fault current amplitude varies with a change in impedance between source and fault.

The main issue with this method is that there should be a good distance between two breakers as the relay would not be able to detect faults if the distance between two zones breaker is less.

Discrimination by both Time and Current:

This method is based on the fact that with an increase in fault current, the clearance time should reduce.

There are three types of inverse time-current characteristic curves:

  • Inverse definite minimum time (standard inverse)
  • Very inverse time
  • Extremely inverse time

Extremely inverse time has the minimum clearance time with an increase in fault current than very inverse time and lastly inverse definite minimum time.

Primary and Backup Protection

Zones of Protection:

For better security of elements that is relay associated with faulty area sense and clear the fault on first priority power system components are divided into the region. Faults can be classified into two with respect to the defined zone:

  1. Internal fault: fault within the zone
  2. External fault: fault outside the zone

Reach point: The farthest point from a relay in a specified zone.

Reach of the relay: Distance between relay and reach point.

Here the power system zones are being overlapped due to reason that no zones remain unprotected.

As each power system element generator, transformer, transmission lines, and others have a different structure, cost, and functionality, they are divided into a separate zone for better security. As fault within a zone can be internal and external, depending upon the type of fault protection scheme can be classified into two types:

Primary Protection:

They are concerned with internal fault and are efficient enough to detect a fault in the least possible time within a zone and gives a trip signal. Primary protection schemes are usually implemented using differential, distance, and directional overcurrent protection.

Differential Protection:

Differential protection works on the current matching principle that is two CTs are connected in a region in such a way that whenever there is a difference in current within that region, the relay gives a trip signal, else no tripping.

They are used in power transformers, generators, and bus bar protection schemes.

Distance Protection:

In transmission lines, it is not possible to implement differential protection. For transmission line protection, distance protection is used which is based on ohm’s law that measures voltage and current, if the measured impedance is less than the transmission line impedance then the relay gives a trip signal.

Directional Overcurrent Protection:

A directional protection scheme becomes functional in the case of a double-end feed system or parallel lines or a ring main system, where a fault gets fed from both sides. It senses the current magnitude and direction for the decision-making purpose.

Backup Protection:

For better reliability purposes, backup protection schemes are used. They are less efficient than primary protection but are used for the purpose, if primary protection does not give a trip signal due to some reason in case of fault, the backup protection trips after some delay. They are also used in detecting external faults. Backup protection is achieved using overcurrent relay.

Coordination Methodology

The following methodology is adopted for the overcurrent protection of the power system:

Data Required:

  1. Single line diagram, indicating rating, manufacturer, and types of each element including C.T, motors, generators, transformer, cables and protective devices (for accurate short circuit calculation and relay coordination)
  2. Impedance of rotating machines and transformers (as they also take part in fault current)
  3. Minimum and maximum fault current. (for time-setting purposes)
  4. Maximum loading ( to get an overload of the system)
  5. Voltage level (for selection of the type of circuit breaker and relay)
  6. Starting and inrush current, damage curves of cables and transformer, induction motor stalling time and acceleration time (these variables are considered in order to prevent nuisance tripping)

Rules:

  1. If possible, relays having similarities in operation should be placed in series.
  2. Relay farthest from the source must have a current setting less than or equal to the relay behind it, as the relay in front requires less current to operate as compared to the relay behind it.

IEEE Standards for Relay Settings:

Coordination for Radial Feeders:

Following example shows the coordination of three relays A, B, and C.

When a fault occurs in front of relay C, it will be sensed by all 3 relays. Here relay C will act as a primary relay and relay B and A as backup, it will be desired that relay C trips first, then relay B if relay C fails to trip, and then relay A if relay B fails to trip. Here time of operation of relay C is adjusted lowest among the two other relays for maximum and minimum fault front of relay C.

When a fault occurs in front of relay B and relay C, it will be sensed by only relay A and B relays. Here relay B will act as a primary relay and relay A as backup, it will be desired that relay B trips first, then relay A if relay B fails to trip. Here time of operation of relay B is minimum than relay A for maximum and minimum fault front of relay C.

Directional Overcurrent Relay Setting for Different Scenarios:

Following are the cases where directional overcurrent protection is used to fulfill the selectivity requirement.

Load Connected to a Generator through Parallel Transmission Line:

In the given system relay 1 & 4 are non-directional relay while 2 & 3 are directional relay with minimum TMS.

Ring System:

In the given system, 1 & 8 are non-directional relays while 3, 5 & 7 are relays that will sense fault in a clockwise direction, and 2, 4 & 6 in counter-clockwise direction that is 2, 3, 4, 5, 6, 7 are directional relays.

In this blog we have understood different types of relays, their settings, and their coordination methodology and in last we have included a brief overview regarding directional overcurrent relay for different types of systems. Relay settings are the essential part of protective scheme for Power System and its coordination is one of the prime focuses of protection for Power System.

We here at AllumiaX perform different types of studies related to the protection of Power system. Engineers at AllumiaX are capable of providing high quality protective device coordination study including Protective Relay Settings and Coordination Services. Get in touch with us at support@allumiax.com

--

--